      Welcome to the official website of Lihong Safety Equipment Engineering (Shanghai) Co., Ltd.!
      Position首頁 > Home > Industrial Safety Products > Safety Controller > Force-guided Safety Relay
      G4SA strong conductance relay
      1726200504472355.png

      ·Various contact combinations: two groups of normally open+two groups of normally closed, three groups of normally open+one group of normally closed.

      ·Force-guided contact structure (according to EN 50205 standard)

      ·Strong load capacity: 6A contact switching ability

      ·Low input power consumption: 360mW

      ·Strong insulation capability: input-output bears 10kV surge voltage.

      ·Environmentally friendly products (RoHS compliant)


      Product selection

      product name

      model

      Contact form

      brand

      safety relay

      G4SA-2A2B

      2NO+2NC

      LHS

      safety relay

      G4SA-3A1B

      3NO+1NC

      LHS

      explain



      Coil parameters

      Rated voltage DC(V)

      Action voltage VDC

      Release voltage VDC

      Maximum voltage VDC

      Coil resistance ω

      24

      ≤18.0

      ≥2.4

      31.2

      1600×1±10%

      Remarks:

      1. The above values are all initial values;

      2. The maximum voltage refers to the maximum voltage that the relay coil can bear in a short time;

      3. For products with rated voltage ≥48V, in order to protect the coil from operation, measures must be taken to suppress the overvoltage of the coil during testing and application (such as connecting diodes in parallel with the coil).

      Coil parameters

      Dimension of external dimension

      40×13×24mm

      Contact

      form Contact form

      2A2B

      3A1B

      Contact resistance (initial)Contact resistance

      ≤100mΩ(1A 6VDC)

      Contact Material material

      Silver alloy

      Contact load (resistance) Contact ratings

      6A 250VAC/30VDC

      Maximum switching voltage Max switching voltage

      400VAC/30VDC

      Maximum switching current Max switching current

      6A

      Maximum switching power Max switching power

      1500VA/180W

      Mechanical life (frequency 300 times /1 minute) Mechanical life

      1×107

      Electrical life (frequency 1S on, 1S off)Electrical life

      1×105次(1NO:6A 250VAC, resistive load, room temperature, 1S on and 9S off)

      coil power Coll power

      約360mW

      insulance Insulation resistance

      1000mΩ(500VDC)

      Dielectric withstand voltage

      Dielictricstength

      Between the same pole contacts Between contacts

      4000VAC 1min

      Disconnect between contacts

      1500VAC 1min

      Contacts and coils Between contacts and coil

      2500VAC 1min(7-8/9-10)

      surge voltage Surge voltage

      10kV(1.2/50μs)

      actuation time Action time

      ≤20ms

      release time Release time

      ≤20ms

      Coil temperature rise Coll Temperature rise

      ≤60K(The coil driving voltage is 1.1 times Un, and the contact current is rated current)

      Stamping resistance  Resistance stamping

      stability Stability

      100m/S2

      intensity Intensity

      980m/S2

      Vibration resistance Vibration Resistance

      10Hz~55Hz 1.5mm double-amplitude

      ambient humidity Ambient humidity

      5%~85%RH

      ambient temperature Ambient temperature

      -40℃~+85℃

      Lead-out form Ambient temperature

      Printed plate

      weight Weight

      About 20g

      package Encapsulation way

      Flux-proof type


      Curve performance diagram

      1726201049360519.png

      (1) Curve refers to 1Z1 type.

      (2) Test conditions: 1NO terminal, resistive load, 250VAC room temperature, 1s on and 9s off.


      outline dimension

      1726201585320928.png

      Remarks:

      1. The dimension tolerance is not indicated for some external dimensions of the product.

      When the overall dimension is less than or equal to 1 mm, the tolerance is ±0.2mm;;

      When the overall dimension is between 1 and 5 mm, the tolerance is ±0.3mm;

      When the overall dimension is greater than 5mm, the tolerance is 0.4 mm..

      2. The dimension tolerance of ±0.1mm is not indicated in the dimension of the installation hole.


      Outline drawing, wiring diagram and mounting hole size

      G4SA-2A2B

      G4SA-3A1B

      1726201962134369.png1726201973396095.png


      Relay matching socket

      1726120041939521.png

      ·The withstand voltage between the coil and the contact is 2500VAC, and the insulation resistance is 1000 mω.

      ·Can be installed by screws or guide rails.

      ·Protect the coil with diode to suppress reverse overvoltage.

      ·With finger protection cover

      ·Keep and take out the self-contained relay.


      Outline drawing, wiring diagram, mounting hole size and circuit diagram

      1726202193547070.png


      Related Products
      Download
      PDF file download
      Video file download
      Previous

      Contact us

      400-881-6062

      Lihong Safety Equipment Engineering (Shanghai) Co., Ltd.

      E-Mail: info@lh-safety.com

      Address: 581 Xiuchuan Road, Chuansha Town, Pudong New District, Shanghai

      (Greenland East Coast International Plaza-Room A 313)

      Copyright ? Lihong Safety Equipment Engineering (Shanghai) Co., Ltd.  ICP19034341-1  Technical Support: lanjujing

      Online service

      Online message

    1. Click to refresh